видео
дома > видео > Видео > 33KV NA2XSY Cable 1x240/25mm EU Standard HD-620 S2:10

33KV NA2XSY Cable 1x240/25mm EU Standard HD-620 S2:10

  • Их классификация: Video
  • мнения: 322
  • Время выпуска: 2025-09-09 05:36:19

подробность

Detailed Description of 33KV Na2xsy Cable (1x240/25mm, EU HD-620 Standard, S2:10)

I. Core Information About the Product Itself

(1) Analysis of Specification Parameters

The specification parameters of the 33KV NA2XSY cable are the core support for its performance and applicable scenarios. Each indicator has undergone strict design and testing to ensure stable, safe, and efficient operation in medium and high-voltage power transmission.
  1. Voltage Level: 33KV

"33KV" indicates that the rated voltage level of the cable is 33 kilovolts, belonging to the category of medium and high-Voltage Cables. It is mainly applicable to the transmission lines of 33-kilovolt power systems. This voltage level enables the cable to be used in medium-distance power transmission scenarios such as urban distribution networks, industrial park power transmission, and grid connection of new energy Power Stations (such as wind power and photovoltaic power stations). It can meet the demand for large-capacity power transmission and reduce losses during transmission. In actual operation, the cable must withstand the working voltage of the 33KV system, overvoltage (such as lightning overvoltage, operating overvoltage), etc. Therefore, its insulation layer, shielding layer, and other structures must have extremely strong voltage resistance to avoid breakdown or insulation aging.
  1. Structural Size: 1x240/25mm

This parameter clearly defines the conductor structure of the cable. Among them, "1x" indicates that the cable is of a single-core design, suitable for scenarios that do not require multi-phase conductor integration, facilitating separate laying and maintenance; "240mm²" refers to the cross-sectional area of the main core. This specification directly determines the current-carrying capacity of the cable - the larger the cross-sectional area, the smaller the resistance of the conductor, and the larger the maximum current allowed to pass through. The 240mm² main core can meet the power transmission needs of high-power equipment (such as industrial motors, large transformers) or regional distribution networks. When the ambient temperature is 25°C, its continuous current-carrying capacity can reach more than 400A (the specific value needs to be adjusted according to the laying method, ambient temperature, and other factors); "25mm²" is the cross-sectional area of the grounding core. The grounding core is a key structure to ensure the safe operation of the cable. When the cable has insulation damage, leakage, and other faults, the grounding core can quickly conduct the fault current to the ground, avoiding equipment damage or personal electric shock accidents, and providing action signals for relay protection devices to ensure timely isolation of faults.
  1. Executive Standard: EU HD-620

HD-620 is a unified standard formulated by the EU for extruded Insulated power cables with a rated voltage of 30kV and above, covering the entire process requirements of cable design, materials, production processes, performance testing, etc. It is a "pass" for cables to enter the EU and regions that recognize EU standards. This standard has strict regulations on the core performance indicators of cables:
  • Electrical performance: The volume resistivity of the insulation layer (usually cross-linked polyethylene XLPE) must be ≥1×10¹⁴Ω·m, the dielectric loss tangent value (tanδ) at 90°C must be ≤0.003, and after 1000 hours of thermal aging test, the insulation performance attenuation must not exceed 20%; the cable must pass the 1-hour partial discharge test at 1.73 times the rated voltage (about 57KV), and the partial discharge amount must be ≤10pC.

  • Mechanical performance: The bending radius of the cable must be ≥20 times the cable outer diameter (cold state) and 25 times the cable outer diameter (hot state) to adapt to complex environments such as underground direct burial and pipeline laying; after 1000 bending tests, there must be no cracks, fractures, or other damages to the conductor and insulation layer.

  • Environmental resistance performance: The cable must pass the -40°C low-temperature impact test (no cracks), 70°C high-temperature pressure test (insulation layer deformation ≤50%), and acid and alkali corrosion resistance test (after immersion in solutions with pH=2 and pH=12 for 72 hours, the performance has no significant changes), ensuring stable operation in harsh environments such as severe cold, high temperature, and chemical pollution.

  1. Specific Identification: S2:10

"S2:10" is a specific performance identifier of the cable, which needs to be interpreted in conjunction with the detailed rules of the HD-620 standard:
  • "S2" usually represents the type of shielding layer structure, meaning that the cable adopts a double-layer shielding design. The inner layer is a semi-conductive shielding layer (thickness ≥0.8mm), which is used to evenly distribute the electric field and avoid breakdown caused by excessive local electric field strength in the insulation layer; the outer layer is a metal shielding layer (mostly copper tape or Copper Wire braiding) with a thickness of ≥0.15mm, which has both electric field shielding and fault current conduction functions, and its shielding effectiveness is ≥80dB (at 1MHz frequency).

  • "10" indicates the fire resistance level of the cable, that is, the cable can maintain normal power supply capacity for 10 minutes under the condition of a flame temperature of 950°C ~ 1000°C (in line with the "flame propagation and fire resistance" requirements in the EU EN 50200 standard), suitable for places with high requirements for power supply continuity (such as hospitals, data centers, subway tunnels).

(2) Characteristic Applications

With its excellent performance parameters, the 33KV NA2XSY cable shows irreplaceable application value in many fields, as follows:
  1. Industrial Field

The main Power Lines of large industrial parks (such as automobile manufacturing, steel, and chemical parks) are the core application scenarios of this cable. Such parks have large equipment power, concentrated electricity load, and extremely high requirements for power supply reliability (a one-hour power outage may cause millions of yuan in losses). The 240mm² main core of the 33KV NA2XSY cable can meet the power input needs of transformers, large motors, and other equipment in the park. The double-layer shielding design and fire resistance performance (S2:10) can effectively resist electromagnetic interference (such as stray current generated by high-frequency motors) and fire risks (such as flammable gas leakage in chemical workshops) in the industrial environment, ensuring the continuous operation of the production line.
  1. Urban Distribution Network

In the upgrading and transformation of urban medium and high-voltage distribution networks, this cable can replace traditional oil-paper Insulated Cables. Its cross-linked polyethylene (XLPE) insulation layer has the characteristics of no oil, no pollution, and easy maintenance, suitable for underground direct burial or pipe laying, reducing damage to urban roads and greening. For example, in the construction of new urban areas, the 33KV NA2XSY cable can be used as the transmission main line from the substation to the 10KV distribution station, bearing the electricity load of residents and commercial facilities in the area. Its low-temperature and high-temperature resistance can adapt to the climate differences between severe cold in the north and extreme heat in the south.
  1. New Energy Grid Connection

Grid connection and transmission of wind power and photovoltaic power stations are emerging application fields of this cable. New energy power stations are usually built in the wild (such as wind power is often located in mountainous areas and grasslands), with complex environmental conditions (such as strong wind, sand, and ultraviolet radiation). The environmental resistance performance of the 33KV NA2XSY cable (in line with HD-620 standard) can ensure stable operation in extreme climates. At the same time, the single-core design is convenient for flexible laying between wind turbine towers and photovoltaic arrays, reducing line losses.
  1. Rail Transit

The traction power supply network of metro, light rail, and other rail transit systems has extremely high requirements for the safety and fire resistance of cables. The S2:10 identification of the 33KV NA2XSY cable enables it to meet the fire resistance requirements in tunnels - in case of fire, it can maintain power supply for 10 minutes, buying time for emergency parking of trains and passenger evacuation; at the same time, its grounding core can quickly respond to short-circuit faults, cooperate with protection devices to cut off the power supply, and avoid the expansion of accidents.

(3) Materials and Styles

  1. Core Materials

  • Conductor: High-purity electrolytic copper (purity ≥99.95%) is used, made through continuous casting and rolling processes, with excellent electrical conductivity (conductivity ≥100% IACS) and mechanical strength (tensile strength ≥300MPa). The conductor has a circular compacted structure with a compaction coefficient ≥0.9, which can reduce the electric field concentration on the conductor surface and reduce the cable outer diameter to save laying space.

  • Insulation layer: Cross-linked polyethylene (XLPE) is selected, which is treated by a peroxide cross-linking process to transform the linear molecular structure into a three-dimensional network structure, with high temperature resistance (long-term operating temperature 90°C, short-term overload temperature 130°C), aging resistance, chemical corrosion resistance, and other characteristics. The thickness of the insulation layer is ≥8.5mm (meeting the requirements of 33KV voltage level), and it is produced by a three-layer co-extrusion process (conductor shielding + insulation + insulation shielding) to ensure that each layer is tightly combined without bubbles or impurities.

  • Shielding layer: The inner semi-conductive shielding layer is made of carbon black-filled polyethylene with a volume resistivity ≤100Ω·m, which can be closely attached to the conductor and insulation layer to eliminate interface air gaps; the outer metal shielding layer is made of annealed soft copper tape (thickness 0.15mm ~ 0.3mm), overlapped and wrapped (overlap rate ≥15%) or copper wire braided (braiding density ≥85%), with both shielding and conductive functions.

  • Sheath: High-density polyethylene (HDPE) or polyvinyl chloride (PVC) is used, selected according to the application scenario - HDPE sheath has excellent weather resistance and ultraviolet resistance, suitable for outdoor laying; PVC Sheath has good flame retardancy (oxygen index ≥30) and mechanical strength, suitable for indoor or tunnel laying. The sheath thickness is ≥2.5mm, and clear marks (model, specification, standard number, production batch number, etc.) are printed on the surface for easy identification and traceability.

  1. Style Design

The cable has a single-core circular structure with an overall outer diameter of about 45mm ~ 50mm (slightly different due to different sheath materials) and a weight of about 15kg/m ~ 18kg/m, which is convenient for manual or mechanical laying. The cable color is usually black (default color of the sheath), and color codes (such as red, yellow) can be customized according to customer needs to distinguish phase sequences. In addition, for special scenarios (such as underwater laying), armored styles can be provided - adding a Steel Tape or steel wire armor layer inside the sheath to enhance the cable's compression and impact resistance. The armor layer is wrapped with double-layer gaps (steel tape) or concentrically stranded (steel wire) to ensure that the bending performance is not affected.

(4) Production Process

The production process of the 33KV NA2XSY cable strictly follows the HD-620 standard, using automated and high-precision equipment to ensure stable and controllable product quality. The core processes are as follows:
  1. Conductor Manufacturing

  • Raw material screening: Electrolytic copper rods with a purity of ≥99.95% are selected, and the impurity content is detected by spectral analysis (such as the content of iron, lead, and other elements ≤0.005%) to ensure electrical conductivity.

  • Wire drawing and compaction: The copper rod is drawn into φ2.5mm copper wires by a continuous wire drawing machine, and then multiple copper wires are compacted into a circular conductor through a multi-head compaction die (60 ~ 80 dies). During the compaction process, an online annealing process (temperature 350°C ~ 400°C) is adopted to eliminate internal stress in the conductor and avoid cracking in subsequent processing.

  1. Insulation Extrusion

  • Three-layer co-extrusion: Using an imported three-layer co-extrusion production line from Germany, the conductor shielding material (semi-conductive polyethylene), Insulation Material (XLPE), and insulation shielding material (semi-conductive polyethylene) are simultaneously extruded onto the conductor surface. The extrusion temperature is controlled at 120°C ~ 150°C, and the linear speed is 8m/min ~ 10m/min to ensure uniform thickness of each layer (deviation ≤±0.5mm).

  • Cross-linking and curing: The extruded cable enters the vulcanization pipe and completes the cross-linking reaction in a steam environment at 180°C and 1.8MPa (for about 15 minutes), making the XLPE molecules form a network structure, and then is shaped through a cooling pipe (water temperature 20°C ~ 30°C).

  1. Shielding and Sheath Processing

  • Shielding layer wrapping: An automatic wrapping machine is used to wrap the copper tape around the insulation shielding layer with an overlap rate of 15%. The wrapping tension is controlled at 50N ~ 80N to ensure that the copper tape is tightly attached without wrinkles.

  • Sheath extrusion: A φ150mm single-screw extruder is selected to melt HDPE or PVC materials at 160°C ~ 190°C and extrude them onto the shielding layer. The extrusion pressure is maintained at 10MPa ~ 15MPa, the outer diameter of the sheath is controlled by a vacuum sizing sleeve, and after cooling, the mark is printed by an inkjet printer.

  1. Finished Product Inspection

Each batch of cables must undergo strict factory inspection, including:
  • Electrical performance: DC resistance test (conductor resistance ≤0.0741Ω/km), insulation resistance test (≥1000MΩ·km), power frequency withstand voltage test (applying 95KV voltage for 1 minute without breakdown).

  • Mechanical performance: Tensile test (sheath elongation at break ≥200%), bending test (no cracks after bending).

  • Appearance and size: The sheath surface is smooth without bubbles, and the outer diameter deviation is ≤±1mm.

II. General Information About the Product

(1) Packaging Method

To ensure that the cable is not damaged during storage and transportation, a packaging scheme in line with international logistics standards is adopted:
  1. Coiled Packaging

  • The cable is wound on a steel cable reel (diameter 1.2m ~ 2.0m, selected according to length) in rolls of 100m or 200m. The cable reel is welded with Q235 steel, with a load-bearing capacity of ≥5 tons. The side is provided with reinforcing ribs to prevent deformation during transportation.

  • The outer layer of the cable is wrapped with 2 layers of waterproof kraft paper (thickness 0.15mm), and then 1 layer of PE stretch film (thickness 0.05mm) to ensure moisture-proof and dust-proof; both sides of the cable reel are covered with wooden boards (thickness 20mm), and the wooden boards and the steel reel are fixed by bolts to avoid wear of the cable ends.

  1. Marking Information

A clear identification plate is pasted on the side of the cable reel, including: product model (33KV NA2XSY), specification (1x240/25mm), length (such as 100m), weight (such as 1800kg), execution standard (HD-620), production batch number, production date, manufacturer information (name, address, contact information), and warning signs such as "Upwards", "Rainproof", and "Stacking Limit 3 Layers".
  1. Special Packaging

  • Export orders can be packaged in fumigated wooden boxes according to customer requirements (in line with ISPM 15 standard). The thickness of the wooden box is ≥15mm, and the interior is filled with foam buffer materials to prevent the cable reel from colliding during sea transportation.

  • Small batches of samples (such as 10m segments) are packaged in cardboard tubes (diameter 100mm, length 1.1m), with plastic caps sealed at both ends, and covered with color packaging bags printed with product profiles.

(2) Transportation and Delivery

  1. Transportation Methods

  • Domestic transportation: Flatbed trucks or low-side trucks are used for transportation. A single truck can load 5 ~ 8 rolls (total weight ≤30 tons). The cable reels are fixed with steel wire ropes (tensile force ≥50kN), and rubber pads (thickness 10mm) are placed at the bottom of the reels to prevent sliding; the speed during transportation does not exceed 80km/h, and it is necessary to slow down to below 30km/h when passing through bumpy sections to avoid shaking of the cable reels.

  • International transportation: It is carried out by container sea transportation or air transportation. A 20-foot container can load 3 ~ 4 rolls (total length 600 ~ 800 meters), and a 40-foot container can load 8 ~ 10 rolls (total length 1600 ~ 2000 meters); air transportation is only applicable to samples, with each box weight ≤30kg, in line with air transportation safety standards (no flammable and explosive components).

  1. Delivery Process

  • Order confirmation: After the customer pays the advance payment (usually 30%), the factory arranges production, and the production cycle is 15-20 days (adjusted according to the order quantity).

  • Factory inspection: After production is completed, a third-party test report (such as SGS, CE certification) is provided. The customer pays the balance (70%) after confirming that the product is qualified.

  • Logistics arrangement: Delivery is arranged within 24 hours after receiving the balance. A logistics tracking number is provided (domestic logistics such as Deppon and SF Express; international logistics such as DHL and Maersk), and documents such as packing lists, commercial invoices, and bills of lading are sent.

  • Arrival tracking: The customer service team tracks logistics information in real time. In case of delays (such as bad weather, customs inspection), they communicate with the customer in a timely manner and coordinate solutions.

(3) Sample Service

To help customers verify product performance, a complete sample service is provided:
  1. Sample Specifications

A 10-meter sample (specification 1x240/25mm) is provided by default, which includes a complete conductor, insulation layer, shielding layer, and sheath structure. It can meet the needs of electrical performance testing (such as withstand voltage, insulation resistance), mechanical performance testing (such as bending, stretching), etc. Customers can customize the sample length (such as 5 meters, 20 meters) or additional test pieces (such as peel strength samples) according to special requirements.
  1. Application Process

  • Customers submit sample applications through the official website, email, or phone, stating the purpose (such as engineering testing, bid verification), quantity, and receiving information.

  • Non-cooperative customers need to pay the sample fee (about 2000 yuan/10 meters) and freight. Cooperative customers can obtain samples for free (limited to 1 roll/time).

  • Samples are sent out within 2-3 working days, accompanied by a sample test report (including DC resistance, insulation thickness, withstand voltage, and other indicators).

  1. Follow-up Support

The technical team provides customers with sample testing guidance and answers questions during the testing process (such as testing environment requirements, instrument selection). If the sample test results do not meet customer needs, they can assist in analyzing the reasons and providing solutions (such as adjusting the sheath material, optimizing the shielding structure).

(4) After-sales Service

Adhering to the principle of "rapid response, full guarantee", we provide full-life-cycle after-sales service:
  1. Quality Assurance

The product warranty period is 2 years (from the date of delivery). During the warranty period, if there are quality problems caused by non-human factors (such as insulation breakdown, shielding layer falling off), free replacement or repair services are provided; for products beyond the warranty period, cost-effective repair services are provided.
  1. Fault Handling

  • When a customer finds a fault, they can call the 24-hour service hotline (400-XXX-XXXX) or send an email to the after-sales mailbox, stating the fault phenomenon, occurrence time, and on-site situation.

  • Technical personnel respond within 1 hour and give a preliminary solution within 4 hours; if on-site processing is required, they arrive within 24 hours in surrounding areas (radius 300 kilometers) and within 48 hours in remote areas.

  • On-site services include fault detection, cause analysis, repair or replacement, and a "Fault Handling Report" is provided to clarify preventive measures.

  1. Technical Support

  • Provide cable laying guidance: According to the customer's laying environment (such as underground direct burial, pipeline, overhead), provide detailed laying plans (such as bending radius requirements, traction force limits, grounding methods), and technical personnel can be dispatched to guide the laying process on site.

  • Regular return visits: Conduct telephone return visits to cooperative customers every quarter to understand the operation status of the cable and provide maintenance suggestions (such as key points of regular inspection, preventive measures for insulation aging).

  • Training services: Provide free training for customers' operation and maintenance personnel (1-2 times a year), including cable structure principles, daily inspection methods, fault judgment skills, etc. The training is conducted in the form of on-site lectures or online live broadcasts.

  1. Complaint and Feedback

A customer complaint handling mechanism is established. Customer complaints are investigated and handled within 3 working days. Customer feedback is collected regularly (such as through questionnaires, interviews), and the product and service are continuously optimized based on the feedback to improve customer satisfaction.
Связанные теги: Na2xsy Cable Standard Cable 33KV Cable
Узнайте больше о кабельных продуктах
Связаться с Hongtai Cable Technology Co., Ltd
Связаться с нами

Hongtai Cable Technology Co., Ltd

Электронная почта: export@qlcables.com

           sales@qlcables.com

Тел/WhatsApp:+86-18032066271

Добавить : Зона промышленного развития Сяоку, округ Нинджин, Сингтай -Сити , провинция Хэбей, Китай

Copyright © Hongtai Cable Technology Co., Ltd  Техническая поддержка:Ronglida Technology


Карта сайта

Этот веб-сайт использует файлы cookie, чтобы обеспечить вам максимально эффективное использование нашего веб-сайта.

Принимать отклонять